SAT-LCL 36KW Rack mounted AC/DC liquid cooling load

With the water cooling of data centers,

SAT-LCL 36KW Rack mounted AC/DC liquid cooling load
SAT-LCL 36KW Rack mounted AC/DC liquid cooling load

SAT-LCL

SAT-LCL 36KW Rack mounted AC/DC liquid cooling load

With the water cooling of data centers,

Contact Aitelong

With the water cooling of data centers, "liquid cooling" technology is the most reliable and feasible solution to reduce the energy consumption of data centers. Liquid cooling load can simulate the actual heat generation and power consumption of real servers in the server room, detect the liquid cooling effect of the server room and the power safety of the server room lines, and provide data basis and testing methods for the reliability of the server room system. The liquid cooling load box adopts a modular design, which is easy to maintain and replace. It can be used alone or in parallel with multiple machines, and each gear can be adjusted.

l Load simulation: can simulate the actual heating situation of the server in the computer room, cooling effect, power supply load capacity, line reliability verification, etc.;

l Control mode: can control the load power increase/decrease through a multi-position switch;

l Temperature protection: when the load temperature exceeds the set safety threshold, an audible and visual alarm prompts;

l Monitoring function: the device can be equipped with an LCD display to display the temperature, flow rate, alarm and other information of the inlet and outlet water;

l Parallel expansion: can realize parallel testing of multiple loads to meet the needs of high-power testing.

  

Technical parameters

Rated voltage/frequency

AC three-phase, single-phase voltage:220V/50Hz

DC 270V

Rated power

36KW (single-phase 12kW@ AC220V/50Hz)

Load step1kW2kW3kW3kW3kW;(ABC three steps)

When the voltage changes, the gear power changes based on AC220V according to Ohm's law.

Load materials

PTC

Power factor

1

Heat transfer efficiency

≥95%

Fully load accuracy

Accuracy≤±5%

Main circuit power interface

2 per phase, interface with protective cover

Load Method

Gear switch(miniature circuit breaker)manual loading

Power control

Adopt the power interface under test for power supply

Isolation level

AC1000Visolation resistance ≥10MΩ

Inlet water temperature

2-100°

Water interface

1 inlet pipe and 1 return pipe, clamp-type quick connector,

pipe diameter: DN25

Pressure

Liquid cooling container or resistor withstands 1.0MPa working pressure, and the ultimate test pressure is 1.5 times the working pressure

Airtightness

No leakage for 2 hours under 1Mpa pressure

Water flow

1-10m3/h

Cooling method

High grade pure water cooling

Isolation grade

F

Protection grade

IP24

Working method

Continuous working

Pipe material

Stainless steel 304

Pannel display

The load panel has a power working indicator light and a fault alarm indicator light.

It has an inlet and outlet water temperature sensor to display the temperature and current, voltage, and power data (LED instrument), and the sensor accuracy is 0.5 level.

Over-heat protection

The load carries the water temperature monitoring of the inlet and outlet. When the water temperature is abnormal, the alarm prompts and the load is unloaded. The upper limit of the inlet and outlet temperature alarm is adjustable (default: 80)

Overcurrent protection

When the switch is in overcurrent protection, the switch trips and cuts off the overcurrent load;

Grounding protection

The ground wire of the load input port is connected to the chassis, and the chassis grounding terminal is for users to use for grounding.

Short circuit protection

The load short-circuit switch trips and cuts off the load

Load modular design

The load adopts modular design and can be used as a single module or in parallel

Size

430mm*720mm*289mm(L*W*H) blue

Weight

55kg

Transportation

The side is equipped with lifting handles for easy transportation;

Working temperature

-15℃~+70

Relative humidity

0-95%RHNon-condensing

Altitude

≤2500m

Atmospheric pressure

86106kPa

Installation conditions

For indoor use, no flammable gas around


AITELONG Support

Product & Project Support

Support for product selection, documentation and field use.

Technical Support

Technical Support

Responsive communication for operation, documentation and after-sales requirements.

Related products

You May Also Like

SAT-AC Battery Conductance Tester
Backup PowerSAT-AC

SAT-AC Battery Conductance Tester

SAT-AC Battery Conductance TesterSAT-AC  Battery Conductance Tester is a multi-function and portable digital instrument to test lead acid stationary battery running condition and parameters quickly and precisely. It can display and record many k...

View Product
SAT-AR Battery Internal Resistance Tester
Backup PowerSAT-AR

SAT-AR Battery Internal Resistance Tester

SAT-AR Battery Internal  Resistance Tester Internationally, resistance test is widely applied in daily battery maintenance instead of voltage check, because resistance is important parameter to test battery quickly and accurately worldwide.SAT-AR...

View Product
SAT-DC200 Series Battery Charger
Backup PowerSAT-DC200

SAT-DC200 Series Battery Charger

SAT-DC200 Series Battery Charger Key Features 1. Intelligent 3 degree charging, auto switch for equalized/floating charging, constant current/voltage. 2. Portable design, small volume, light weight ,easy to move.  3. Upload the test d...

View Product
SAT-DC500 Series Battery Charge and Discharge
Backup PowerSAT-DC500

SAT-DC500 Series Battery Charge and Discharge

SAT-DC500 Series Battery Charge and DischargeKey Feature1. 5 in 1: Charge, discharge, cell monitor, online monitor, and battery activator.2. Individual cell wireless monitor function, each module can monitor 12 single cells.3. USB port...

View Product